Product Overview
YBW series prefabricated substations integrate high-voltage devices, transformers and low-voltage devices into compact complete distribution units, to receive and distribute power for high-rise buildings, residential zones, industrial parks, mines, oil fields and temporary construction sites.They feature high integration, compact layout, easy maintenance and mobility.
Occupying 1/10-1/5 of the land area of conventional masonry substations at the same capacity, they cut design workload, construction work and overall investment. Compatible with ring main, dual-power and radial terminal distribution systems, they are widely adopted for new build and upgrade of urban and rural substations.
Model and Meaning

Service Conditions
- 1. Ambient air temperature: upper limit ≤ 40 ℃, lower limit -10 ℃
- 2. Solar radiation ≤ 1000W/m²
- 3. Altitude ≤ 1000m
- 4. Ice coating thickness ≤ 20mm
- 5. Wind speed ≤ 35m/s
- 6. Humidity: daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%;daily average water vapor partial pressure ≤ 2.2kPa; monthly average water vapor partial pressure ≤ 1.8kPa
- 7. Seismic intensity ≤ 8 degrees
- 8. Sites without fire risk, explosion hazard, heavy contamination, chemical corrosion and severe vibration.
- Note: If special operating conditions apply, please consult the manufacturer before placing orders.
Structural Features
- The enclosure has high-voltage, transformer and low-voltage compartments. Multiple supply modes, two transformer types and customizable low-voltage functions are available.
- Anti-misoperation interlocks are equipped in the high-voltage compartment. Transformers can be track-mounted for easy removal, with built-in compartment lighting for convenient maintenance.
- Combined natural and forced ventilation with thermostatic fans ensures reliable operation.
- Color steel casing provides corrosion, water and dust protection for long outdoor use.
Technical Parameters
YBW-12/0.4 Outdoor Prefabricated Substation
| Name | Unit | High voltage electrical equipment | Transformer | Low voltage electrical equipment |
| Rated voltage | kv | 10 | 10/0.4 | 0.4 |
| Rated current | A | 630 | 100~2500 | |
| Rated frequency | Hz | 50 | 50 | 50 |
| Rated Capacity | kVA | 100~1250 | ||
| Rated thermal stability current | kA | 20/45 | 30/15 | |
| Rated dynamic current(peak) | kA | 50 | 63 | |
| Rated short circuit current (peak) | kA | 50 | 15~30 | |
| Rated breaking shortcircuit curreet | kA | 31.5(fuse) | ||
| Rated breaking load current | A | 630 | ||
| 1min power frequency withstand voltage | kA | 42 for earth /phase-to-phase,48 across break gap | 35/28(5min) | 2.0/2.5 |
| Lightning impulse withstand voltage | kA | 75 for earth /phase-to-phase,85 across break gap | 75 | |
| Shell protection grade | IP33D/IP23D(Transformer Enclosure) | |||
| Noise level | dB | Oil-immersed s55, Dry-type s65 | ||
| Number of loops | piece | 1-6 | 2 | 4-30 |
| Maximum reactive power compensation on the low voltage side | Kvar | 300 | ||